Inpu Measuring variables position, liquid level Stroke length – Analog profile/rod models: 50…2500 mm (longer stroke lengths are available on a custom basis) – Start/Stop profile model: 50…5000 mm, rod model: 50…7600 mm Output Voltage 0…10 / 10…0 / -10…+10 / +10…-10 VDC (min. load controller: > 5 kOhms) Current 4(0)…20 mA / 20…4(0) mA (min/max. load: 0/500 Ohms) Start/Stop pulse RS422 serial differential signal Accuracy Position measurement: – Null/Span adjustment 100 % of electrical stroke (min. range 50 mm) – Resolution analog: infinite digital (start/stop): 0.1 mm; 0.01; 0.005 mm (controller dependent) – Linearity 1 < ± 0.02 % F.S. (minimum ± 50 μm) – Repeatability < ± 0.001 % F.S. (minimum ± 2.5 μm) – Hysteresis < 4 μm – Update time analog: < 1 ms typical digital (start/stop): controller and stroke dependent – Ripple < 0.01 % F.S. Operating conditions Magnet speed any Operating temperature -40 °C…+80 °C Dew point, humidity 90% rel. humidity, no condensation Ingress protection 2 profile: IP 65, rod: IP 67, IP 68 for cable outlet Shock test 100 g single hit, IEC-Standard 60068-2-27 Vibration test 15 g / 10…2000 Hz, IEC-Standard 60068-2-6 (resonance frequencies excluded) EMC test Electromagnetic emission EN 61000-6-4 (for use in industrial environment) Electromagnetic immunity EN 61000-6-2 The sensor meets the requirements of the EC directives and is marked with CE Design,material Diagnostic display LEDs beside connector Profile model: Sensor head aluminum Sensor stroke aluminum Position magnet magnet slider or removable U-magnet Rod model: Sensor head aluminum Rod with flange stainless steel 1.4301 / AISI 304 -Pressure rating 350 bar, 700 bar peak Position magnet Ring magnets, U-magnets Installation Mounting position any orientation Profile movable mounting clamps or T-slot nuts in base channel Rod threaded flange M18 x 1,5 or 3/4″ -16 UNF-3A, hex nut M18 Position magnet mounting plate and screws from antimagnetic material Electrical connection Connection type 6 pin connector Supply voltage 24 VDC (-15 / +20 %) – Polarity protection up to -30 VDC – Overvoltage protection up to 36 VDC Current drain 100 mA typical Ripple < 0.28 Vpp Electric strength 500 VDC (DC ground to machine ground)
|